DALI-Strom – an
Tabelle Speicherbank 2
|
Adresse |
Beschreibung |
Vorgabewert |
Speicherart |
|---|---|---|---|
|
0x00 |
Address and last accessible memory location |
0x03 |
ROM |
|
0x01 |
Indicator byte (manufacture definable) |
0x00 |
beliebig |
|
0x02 |
Memory bank lock byte (<>0x55 = Read Only else Read/Write) |
0xFF |
RAM |
|
0x03 |
PIR sensitivity segment A (MR, LR and HC detectors) 4 = MAX, 3 = HIGH, 2 = LOW, 1 = MIN, 0 = OFF |
0x03 |
NVM |
|
0x04 |
PIR sensitivity segment B (LR and HC detectors) 4 = MAX, 3 = HIGH, 2 = LOW, 1 = MIN, 0 = OFF |
0x03 |
NVM |
|
0x05 |
PIR sensitivity segment C (LR and HC detectors) 4 = MAX, 3 = HIGH, 2 = LOW, 1 = MIN, 0 = OFF |
0x03 |
NVM |
|
0x06 |
LUX range 0 = NORMAL, 0 – 1023 lux, 10 bit 1 = HIGH, 0 – 10360 lux, 14 bit |
0x00 |
NVM |
|
0x07 |
Bluetooth® communication 0 = enabled, 1 = disabled |
0x00 |
NVM |
Der Melder wird neu gestartet, wenn die Bluetooth®-Kommunikation deaktiviert oder wieder aktiviert wird. Dies dauert etwa 100 - 500 ms.