Niko Home Control is evolving into MOTIV Building Control. MOTIV is a new brand for intelligent building automation. Built on the trusted foundation of Niko Home Control, MOTIV solutions are designed to make buildings work more naturally for the people inside them. MOTIV helps professionals create smarter, more comfortable buildings. With technology that works quietly in the background. All existing Niko Home Control solutions remain fully compatible with MOTIV. Over time, the full portfolio will move to the MOTIV brand. Discover MOTIV at niko.eu/MOTIV
Hardware Manual Fuse Switch Disconnectors
English Danish Dutch French German Slovak Swedish Polish
English Danish Dutch French German Slovak Swedish Polish

Maintenance and troubleshooting of CORON® 2

When the fuse link is blown, it is recommended to replace the whole fuse plug with a spare one to avoid touching the hot fuse link. Spare fuse plugs are readily available if you have installed a cassette with fuse plugs on the DIN rail.

BURN HAZARD: A blown fuse link can have a temperature above 100°C. Never touch it directly with your fingers.

Step 1

Switch OFF.

https://dam.nikocdn.eu/asset/168036/guideImage/61-033_TG005.png
Step 2

Pull out the fuse plug.

https://dam.nikocdn.eu/asset/168034/guideImage/61-033_TG003.png
https://dam.nikocdn.eu/asset/168035/guideImage/61-033_TG004.png
Step 3

Insert the new fuse link.

Step 4

Switch on.

Coron

Lockout procedure

To prevent accidental energisation during installation or maintenance, the fuse switch disconnector can be locked in the OFF position using a padlock.

Step 1

Switch OFF the CORON® 2 fuse switch disconnector.

Step 2

Pull out the fuse plug until the locking holes are aligned.

Step 3

Insert the padlock through the locking holes.

image-20260727-141808.png
Step 4

Verify that the fuse switch disconnector is securely locked in the OFF position before starting any work on the installation.

Only authorised personnel may remove the padlock and restore power after the work has been completed!