Hardware Manual Fuse Switch Disconnectors

Installation of CORON® 2

The installation should be carried out by a qualified installer and in accordance with the regulations of the local distribution system operator.

The images below are for the 3 Pol. version (61-033); the installation for the 3 Pol.+N (61-034) is similar.

Step 1

Click onto the DIN rail, according to IEC/EN 60715.

  • Pay attention to the rated diversity factor (RDF) according to IEC/EN 61439-1.

  • It is recommended to mount a box with fuse plugs on the DIN rail next to the fuse(s), to make spare fuse plugs readily available. Replacing a blown fuse plug with a spare one avoids touching the hot fuse.

step1

Step 2

Only use suitable wires:

  • Copper

  • Rigid, stranded or flexible

  • Cross section 1,5 – 35 mm2

Strip the wires. Use ferrules for flexible wires.

https://s3-eu-west-1.amazonaws.com/guideimages/Manuals/Tytan/961-0110300_TG011.png

Step 3

Feed the wires at the top or at the bottom of the fuse. Secure with 3 Nm, using a PZ2 screw driver.

Use the wiring diagram to connect the wires correctly.

step3

Step 4

Remove the placeholder and insert the fuse link. Depending on the chosen fuse link, use the appropriate spacers:

https://dam.nikocdn.eu/asset/168034/guideImage/61-033_TG003.png
Step4

Step 5

Switch ON.

Step5

Step 6

Check the fuse within 24 hours after switching ON:

  • The average operation temperature must be less or equal to 35 °C.

  • The terminals must remain secured at 3 Nm.