Zehnder: Dirty filter notification via wired connection
What do you need?
Niko requirements
Your Niko Home Control installation meets the following requirements:
It has a connected controller II.
It is configured with the most recent programming software.
You need the following connections and additional products:
Install and connect a digital potential-free sensor module (550-00210).
If the output contact on your ventilation system is not potential-free, you need an additional potential-free contact module.
Zehnder requirements
Your system meets the following requirements:
Your ventilation device has an output contact that signals when the filter is dirty.
It is compatible with the Niko module (see Niko requirements).
Please note that not all ventilation systems that you can control via Niko Home Control are equipped with the output contact required for the filter notifications.
Your system is one of the following Zehnder products*:
The table shows the relevant contacts that are present on each product. If a type of contact is not present, it is shown as “-”.
Output contact that signals when the filter is dirty | |
---|---|
ComfoAir Flex | Error contact |
ComfoD 350 Luxe | Error contact |
ComfoAir Q | Error contact (connector 5) |
*Consult the website of the supplier for detailed specifications and the latest products.
Wiring diagrams
Consult the manufacturer’s manual for the full installation procedure and the necessary settings.
Via potential-free output contact
The output contacts of most ventilation systems are potential-free, allowing a direct connection to the Niko sensor module.
Connect contact 1 on the Niko sensor module to the output on the ventilation system that signals when the filter is dirty, as shown in the wiring diagram.
Via 230 V or 12/24 V output contact
If the contacts of your ventilation system are not potential-free, you additionally need an appropriate potential-free contact module.
Connect contact 1 on the Niko sensor module to the output on the ventilation system that signals when the filter is dirty, as shown in the wiring diagram.
230 V output contact | 12/24 V output contact |
---|---|
*230 V to potential-free contact module (e.g. Finder 22.32.0.230.1xx0) | *12 V to potential-free contact module (e.g. Finder 22.32.0.012.1xx0) or 24 V to potential-free contact module (e.g. Finder 22.32.0.024.1xx0) |
Programming
Configure the potential-free sensor module and create an informative notification via the Niko Home Control programming software. For more information, see https://guide.niko.eu/en/smnhc2/lv/creating-notifications.