DescriptionThere are 3-fold or 6-fold switching modules available. This allows you to switch three or six circuits respectively.
|
Type of lighting | Maximum RMS current |
---|---|
energy-saving lamps (CFLi), LEDs and fluorescent lighting with electronic control gear – | 3A |
fluorescent lamps (parallel compensated) | 6A |
fluorescent lamps (non-compensated or serial-compensated) | 10A |
low-voltage halogen lamps with ferromagnetic or electronic transformers | 10A |
incandescent lamps, 230 V halogen lamps (resistive load) | 16A |
Installation
Connection diagrams
Note |
---|
|
Follow the steps below to install the module:
- Press the switching module onto the DIN rail until it clicks into place.
- Make a single-phase connection from the mains voltage to the L screw terminals.,The three-fold switching module has three independent L screw terminals, which means three power circuits can be connected. In the six-fold switching module, all six screw terminals at the bottom are looped into two groups of three, which means two power circuits can be connected.
- The switching circuits you wish to connect can now be connected to screw terminals 1’-3’ or 1’-6’.
- Group all neutral conductors and connect these to an N screw terminal.
- Connect the switching module to the module before it. Slide the sliding contact of this module to the right until it clicks into the switching module. This will ensure that the bus and the power supply voltage are connected.
Error codes
When the module is functioning properly, the STATUS LED will light up in TEST mode only. If one or several errors occur, the LED will blink to indicate the error code of the error with the highest priority. The table below provides an overview of all error codes.
LED | ACTION | ERROR | POSSIBLE SOLUTIONS |
---|---|---|---|
STATUS LED | Blinks – one pulse per two | Software error | Incorrect software version.* |
Technical data
Three-fold switching module
- maximum load: 230 V – 16 A per switching contact
- Maximum load across the module: 230 V – 40 A 3 separate switching circuits possible in the same phase
- dimensions: DIN 2E
- sliding contact to connect the module to the following module on the DIN rail
- 2 x 4 screw terminals for 3 x 1.5 mm² or 2 x 2.5 mm² or 1 x 4 mm²
- CE marked
- ambient temperature: 0 - 45°C
Six-fold switching module
- maximum load: 230 V – 16 A per switching contact
- total maximum load of the module: 230 V – 32 A
- 2 groups with 3 switching contacts each
- dimensions: DIN 4E
- sliding contact to connect the module to the following module on the DIN rail
- 2 x 8 screw terminals for 3 x 1.5 mm² or 2 x 2.5 mm² or 1 x 4 mm²
- CE marked
- ambient temperature: 0 - 45°C
Sv translation | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||||||||||||
BeschrijvingDe schakelmodules bestaan in drievoudige of zesvoudige uitvoering. Hiermee kun je respectievelijk drie of zes kringen schakelen. OverzichtWerkingHet bussignaal van de connected controller activeert één of meerdere outputs van de schakelmodule. Je kunt de outputs ook manueel activeren of deactiveren met de knoppen op de schakelmodule. Let erop dat deze activering of deactivering tijdelijk is want dit wordt overschreven bij de eerstvolgende buscommunicatie. Outputs activeren of deactiveren gebeurt via energiezuinige bistabiele relais in de module. De toestand van het relais wijzigt alleen als de controller of één van de schakelknoppen een datapuls genereert. Toegelaten belastingenVolgende tabel geeft een overzicht van de maximale belasting per type verlichting.
InstallatieAansluitschema’s
Om de module te installeren: 1 Klik de schakelmodule op een DIN-rail. 2 Sluit de netspanning enkelfasig aan op de L-schroefklemmen. De drievoudige schakelmodule heeft drie afzonderlijke L-schroefklemmen. Je kunt dus drie voedingskringen aansluiten. Bij de zesvoudige schakelmodule zijn de zes schroefklemmen onderaan doorgelust in twee groepen van drie. Je kunt dus twee voedingskringen aansluiten. 3 Sluit de schakelkringen die je wilt schakelen, aan op de schroefklemmen 1’-3’ of 1’-6’. 4 Groepeer de nuldraden en sluit ze aan op een N-schroefklem. 5 Verbind de schakelmodule met de module ervoor. Schuif de schuifbrug van deze module naar rechts tot ze vastklikt in de schakelmodule. Hierdoor zijn de bus en de voedingsspanning doorgegeven. FoutcodesAls de module normaal functioneert, licht de STATUS-led enkel op in TEST-mode. Als er één of meerdere fouten optreden, gaat hij knipperen om de foutcode weer te geven van de fout met de hoogste prioriteit. Een overzicht van de foutcodes vind je in volgende tabel.
Technische gegevensDrievoudige schakelmodule
Zesvoudige schakelmodule
|
Sv translation | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||||||||||||
DescriptionLes modules de commutation sont disponibles dans les versions triple et sextuple. Cela vous permet de commuter trois ou six circuits, respectivement. SynthèseLe signal de bus de l'unité de contrôle connectée active une ou plusieurs sorties du module de commutation. Vous pouvez aussi activer et désactiver les sorties manuellement à l'aide des boutons situés sur le module de commutation. Attention : cette activation ou désactivation n'est que temporaire, car elle est écrasée lors de la communication suivante sur le bus.FonctionnementL'activation ou la désactivation des sorties se fait à l'aide de relais bistables peu énergivores situés dans le module. L'état du relais ne change que si l'unité de contrôle ou un bouton de commutation génère une impulsion de données. Charges autoriséesLe tableau ci-dessous donne un aperçu de la charge maximale autorisée par type d'éclairage.
InstallationSchémas de raccordement
Pour installer le module:
Codes d'erreurSi le module fonctionne normalement, la LED D'ÉTAT ne s’allume qu’en mode TEST. Si une ou plusieurs erreurs surviennent, cette LED clignote afin d’indiquer le code de l’erreur ayant la plus grande priorité. Le tableau ci-dessous présente un aperçu des codes d'erreur.
Données techniquesModule de commutation triple
Module de commutation sextuple
|
Sv translation | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||||||||||||
OpisK dispozícii sú trojnásobné a šesťnásobné spínacie moduly. To vám umožňuje jednotlivo prepínať medzi tromi alebo šiestimi okruhmi.
|
Typ osvetlenia | Maximálny efektívny prúd |
---|---|
energeticky úsporné žiarivky (CFLi), LED diódy a žiarivky s elektronickým predradníkom – | 3A |
žiarivky (paralelne kompenzované) | 6A |
žiarivky (nekompenzované alebo sériovo kompenzované) | 10A |
nízkonapäťové halogénové žiarovky s feromagnetickými alebo elektronickými transformátormi | 10A |
žiarovky, halogénové žiarovky na 230 V (odporová záťaž) | 16A |
Inštalácia
Schémy zapojenia
Note |
---|
|
Pri inštalácii modulu postupujte podľa nasledujúcich pokynov:
- Zatlačte spínací modul na DIN lištu, až kým nezacvakne na miesto.
- Vytvorte jednofázové prepojenie zo sieťového napájania na L skrutkové svorky. Trojnásobný spínací modul má tri samostatné L skrutkové svorky, čo znamená, že je možné pripojiť až tri napájacie obvody. V šesťnásobnom spínacom module je všetkých šesť skrutkových svoriek zapojených do obvodov (2 skupiny po troch skrutkách), čiže je možné pripojiť dva napájacie obvody.
- Spínacie obvody, ktoré si želáte pripojiť, môžete teraz pripojiť skrutkové svorky 1"-3" alebo 1"-6".
- Zoskupte všetky nulové vodiče a pripojte ich na jednu N skrutkovú svorku.
- Pripojte spínací modul k modulu, ktorý sa nachádza pred ním. Posuňte posuvný kontakt tohto modulu smerom doprava, kým nezacvakne do spínacieho modulu. Tým sa zabezpečí prepojenie napájacieho zdroja a zbernice.
Chybové hlásenia
Ak modul funguje správne, STATUS LED (stavová LED) sa rozsvieti iba v režime TEST (testovací). Ak dôjde k jednej alebo viacerým chybám, LED bude blikať, pričom ako prvú bude indikovať chybu s najvyššou prioritou. Nižšie uvedená tabuľka uvádza prehľad všetkých chybových hlásení.
LED | AKCIA | CHYBA | MOŽNÉ RIEŠENIA |
---|---|---|---|
STAVOVÁ LED | Bliká – jeden impulz za dve | Softvérová chyba | Nesprávna verzia softvéru.* |
Technické údaje
Trojnásobný spínací modul
- maximálna záťaž: 230 V – 16 A na spínací kontakt
- Celková maximálna záťaž tohto modulu: 230 V – 40 A na jednej fáze je možné mať 3 samostatné spínacie obvody
- rozmery: DIN 2E
- posuvný kontakt na pripojenie modulu na nasledujúci modul na DIN lište
- 2 x 4 skrutkové svorky pre 3 x 1,5 mm² alebo 2 x 2,5 mm² alebo 1 x 4 mm²
- CE označenie
- prevádzková teplota: 0 až 45°C
Šesťnásobný spínací modul
- maximálna záťaž: 230 V – 16 A na spínací kontakt
- celková maximálna záťaž tohto modulu: 230 V – 32 A
- 2 skupiny, každá s tromi kontaktmi
- rozmery: DIN 4E
- posuvný kontakt na pripojenie modulu na nasledujúci modul na DIN lište
- 2 x 8 skrutkové svorky pre 3 x 1,5 mm² alebo 2 x 2,5 mm² alebo 1 x 4 mm²
- CE označenie
- prevádzková teplota: 0 až 45°C
Sv translation | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||||||||||||
BeskrivelseDer kan fås 3-dobbelte og 6-dobbelte koblingsmoduler Med dem kan du koble henholdsvis tre og seks kredsløb.
|
Belysningstype | Maksimal RMS-strøm |
---|---|
Sparepærer (CFLi), LED og lysstofrør med elektronisk drev – | 3A |
Lysstofrør (parallelt-kompenseret) | 6A |
Lysstofrør (ikke-kompenseret eller serie-kompenseret) | 10A |
Lavspændingshalogenlamper med ferromagnetisk eller elektronisk transformer | 10A |
Glødelamper og 230 V halogenlamper (resistiv belastning) | 16A |
Installation
Forbindelsesdiagrammer
Note |
---|
|
Følg trinene herunder ved installation af modulet:
- Tryk koblingsmodulet på DIN-skinnen, indtil den klikker på plads.
- Lav en enkeltfaset forbindelse fra strømforsyningen til L skrueterminalerne. Det 3-dobbelte koblingsmodul har 3 uafhængige L skrueterminaler, hvilket betyder, at 3 strømkredse kan tilsluttes. På det 6-dobbelte koblingsmodul er alle 6 skrueterminaler i bunden sløjfet i 2 grupper af 3, hvilket betyder, at 2 strømkredse kan tilsluttes.
- De kredsløb, du ønsker at forbinde, kan nu forbindes til skrueterminalerne 1’-3’ eller 1’-6’.
- Saml alle nul-ledere, og forbind dem på en N skrueterminal.
- Forbind koblingsmodulet til modulet før det. Lad skydekontakten på dette modul glide til højre, indtil den klikker på koblingsmodulet. Dette vil sikre, at bussen og strømforsyningen er forbundet.
Fejlkoder
Når modulet fungerer korrekt, lyser status-LED’en kun op i TEST-funktion. I tilfælde af én eller flere fejl blinker LED’en for at indikere fejlkoden for fejlen med den højeste prioritet. Tabellen herunder giver en oversigt over alle fejlkoder.
LED | PROGRAMMERING | FEJL | MULIGE LØSNINGER |
---|---|---|---|
STATUS LED | Blinker – en pulsering pr. to | Softwarefejl | Forkert softwareversion.* |
Tekniske data
3-dobbelt koblingsmodul
- Maks. belastning: 230 V – 16 A pr. kanal
- Maksimal belastning i modulet: 230 V – 40 A, 3 separate koblingskredsløb tilladt på samme fase
- Størrelse: DIN 2E
- Skydekontakt til tilslutning af næste enhed på DIN-skinnen
- 2 x 4 skrueklemmer til 3 x 1,5 mm² eller 2 x 2,5 mm² eller 1 x 4 mm²
- CE-mærket
- Omgivelsestemperatur: 0-45 °C
Seks-dobbelt koblingsmodul
- Maks. belastning: 230 V – 16 A pr. kanal
- Modulets samlede maksimale belastning: 230 V – 32 A
- 2 grupper med 3 skiftekontakter hver
- Dimensioner: DIN 4E
- Skydekontakt til tilslutning af næste enhed på DIN-skinnen
- 2 x 8 skrueklemmer til 3 x 1,5 mm² eller 2 x 2,5 mm² eller 1 x 4 mm²
- CE-mærket
- Omgivelsestemperatur: 0-45 °C
Sv translation | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||||||||||||
BeskrivningDet finns trefaldiga och sexfaldiga kopplingsaktorer tillgängliga. Med dem kan du koppla tre respektive sex kretsar.
|
Typ av belysning | Maximal RMS-ström |
---|---|
lågenergilampor (CFLi), LED-lampor och lysrör med elektroniskt förkopplingsdon – | 3 A |
lysrör (parallellkompenserade) | 6 A |
lysrör (ej kompenserade eller seriekompenserade): | 10 A |
lågspänningshalogenlampor med ferromagnetisk eller elektronisk transformator | 10 A |
glödlampor, 230 V-halogenlampor (resistiv last) | 16 A |
Installation
Kopplingsscheman
Note |
---|
|
Följ stegen nedan för att installera aktorn:
- Tryck fast kopplingsaktorn på DIN-skenan tills den klickar på plats.
- Gör en enfasanslutning från nätspänningen till L-skruvplintarna. Den trefaldiga kopplingsaktorn har tre oberoende L-skruvplintar vilket innebär att tre strömkretsar kan anslutas. I den sexfaldiga kopplingsaktorn är alla sex skruvplintarna nedtill loopade till två grupper om tre, vilket innebär att två strömkretsar kan anslutas.
- Kopplingskretsarna som du vill ansluta kan nu anslutas till skruvplintarna 1’-3’ eller 1’-6’.
- Gruppera alla neutralledare och anslut dem till N-skruvplinten.
- Anslut kopplingsaktorn till föregående modul. För glidkontakten på den modulen åt höger tills den klickar in i kopplingsaktorn. Det säkerställer att buss- och försörjningsspänningen är ansluten.
Felkoder
När modulen fungerar som den ska kommer STATUS LED-lampan endast att lysa i TEST-läge. Om ett eller flera fel inträffar kommer LED-lampan att blinka för att ange felkoden för felet med högsta prioritet. Tabellen nedan ger en översikt över alla felkoder.
LED | ÅTGÄRD | FEL | MÖJLIGA LÖSNINGAR |
---|---|---|---|
STATUS-LED | Blinkar – en puls per två | Programvarufel | Felaktig programvaruversion.* |
Tekniska data
Trefaldig kopplingsaktor
- max. belastning: 230 V – 16 A per kanal
- Maximal belastning för modulen: 230 V – 40 A 3 separata kopplingskretsar möjliga i samma fas
- storlek: DIN 2E
- glidkontakt för att ansluta modulen till efterföljande modul på DIN-skenan
- 2 x 4 skruvterminaler för 3 x 1,5 mm² eller 2 x 2,5 mm² eller 1 x 4 mm²
- CE-märkt
- omgivningstemperatur: 0–45 °C
Sexfaldig kopplingsaktor
- max. belastning: 230 V – 16 A per kanal
- total maximal belastning för modulen: 230 V – 32 A
- 2 fasanslutningar med 3 kanaler vardera
- storlek: DIN 4E
- glidkontakt för att ansluta modulen till efterföljande modul på DIN-skenan
- 2 x 8 skruvterminaler för 3 x 1,5 mm² eller 2 x 2,5 mm² eller 1 x 4 mm²
- CE-märkt
- omgivningstemperatur: 0–45 °C
Sv translation | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||||||||||||
BeschreibungEs sind Dreifach- oder Sechsfach-Schaltmodule erhältlich. Damit lassen sich drei bzw. sechs Schaltkreise schalten.
|
Art der Beleuchtung | Strom des maximalen quadratischen Mittelwerts |
---|---|
Energiesparlampen (CFLi), LEDs und Leuchtstofflampen mit elektronischen Vorschaltgeräten - | 3A |
Leuchtstofflampen (parallel kompensiert) | 6A |
Leuchtstofflampen (nicht kompensiert oder in Reihe kompensiert) | 10A |
Niederspannung-Halogenlampen mit Wickeltransformator oder elektronischem Transformator | 10A |
Glühlampen, 230-V-Halogenlampen (ohmsche Last) | 16A |
Installation
Anschlusspläne
Note |
---|
|
Installieren Sie das Modul wie nachfolgend beschrieben:
- Drücken Sie das Schaltmodul auf die DIN-Schiene, bis es einrastet.
- Stellen Sie einen einphasigen Anschluss der Netzspannung an den L-Schraubklemmen her. Das Dreifach-Schaltmodul hat drei unabhängige L-Schraubklemmen, sodass drei Schaltkreise angeschlossen werden können. Beim Sechsfach-Schaltmodul werden alle sechs Schraubklemmen an der Unterseite in zwei Dreiergruppen durchgeschleift, sodass zwei Schaltkreise angeschlossen werden können.
- Die anzuschließenden Schaltkreise können nun an die Schraubklemmen 1'-3' oder 1'-6' angeschlossen werden.
- Fassen Sie alle Neutralleiter zusammen und schließen Sie diese an eine N-Schraubklemme an.
- Verbinden Sie das Schaltmodul mit dem Modul davor. Schieben Sie das Schiebeverbindungsstück dieses Moduls nach rechts, bis es in das Schaltmodul einrastet. So wird gewährleistet, dass Bus und Versorgungsspannung verbunden sind.
Fehlercodes
Wenn das Modul ordnungsgemäß funktioniert, leuchtet die STATUS-LED nur im TEST-Modus. Wenn ein oder mehrere Fehler auftreten, blinkt die LED, um den Fehlercode des Fehlers mit der höchsten Priorität anzuzeigen. Die folgende Tabelle bietet eine Übersicht aller Fehlercodes.
LED | AKTION | FEHLER | MÖGLICHE LÖSUNGEN |
---|---|---|---|
STATUS-LED | Blinkt - ein Impuls alle zwei | Softwarefehler | Falsche Software-Version.* |
Technische Daten
Dreifach-Schaltmodul
- maximale Last: 230 V – 16 A je Schaltkontakt
- Maximale Last für das Modul: 230 V - 40 A 3 getrennte Schaltkreise in derselben Phase möglich
- Abmessungen: DIN 2E
- Schiebeverbindungsstück zum Verbinden des Moduls mit dem nächsten DIN-Schienen-Modul
- 2 x 4 Schraubklemmen für 3 x 1,5 mm² oder 2 x 2,5 mm² oder 1 x 4 mm²
- CE-Kennzeichnung
- Umgebungstemperatur: 0 - 45 °C
Sechsfach-Schaltmodul
- maximale Last: 230 V – 16 A je Schaltkontakt
- maximale Gesamtlast für das Modul: 230 V – 32 A
- 2 Gruppen mit je 3 Schaltkontakten
- Abmessungen: DIN 4E
- Schiebeverbindungsstück zum Verbinden des Moduls mit dem nächsten DIN-Schienen-Modul
- 2 x 8 Schraubklemmen für 3 x 1,5 mm² oder 2 x 2,5 mm² oder 1 x 4 mm²
- CE-Kennzeichnung
- Umgebungstemperatur: 0 - 45 °C