Skip to main content
Skip table of contents

BMS-programvareinnstillinger for P40/M40-sensorer

DALI-strøm – PÅ

Minnetabell 2

Adresse

Beskrivelse

Standardverdi

Minnetype

0 x 00

Address and last accessible memory locationBlank

0 x 03

ROM

0 x 01

Indicator byte (manufacture definable)Blank

0 x 00

noen

0 x 02

Memory bank lock byte (<>0x55 = Read Only else Read/Write)Blank

0 x FF

RAM

0 x 03

PIR sensitivity segment A (MR, LR and HC detectors)Blank

4 = MAX, 3 = HIGH, 2 = LOW, 1 = MIN, 0 = OFFBlank

0 x 03

NVM

0 x 04

PIR sensitivity segment B (LR and HC detectors)Blank

4 = MAX, 3 = HIGH, 2 = LOW, 1 = MIN, 0 = OFFBlank

0 x 03

NVM

0 x 05

PIR sensitivity segment C (LR and HC detectors)Blank

4 = MAX, 3 = HIGH, 2 = LOW, 1 = MIN, 0 = OFFBlank

0 x 03

NVM

0 x 06

LUX rangeBlank

0 = NORMAL, 0 – 1023 lux, 10 bitBlank

1 = HIGH, 0 – 10360 lux, 14 bitBlank

0 x 00

NVM

0 x 07

Bluetooth® communicationBlank

0 = enabled, 1 = disabledBlank

0 x 00

NVM

Sensoren starter på nytt når kommunikasjon via Bluetooth® er deaktivert eller reaktivert. Dette varer i ca. 100–500 ms.